96 Avocent PM PDU Installer/User Guide
Appendix C: Replacing the Fuses (For Service Personnel Only)
This product contains replaceable fuses. To avoid serious injury and/or damage to your Avocent
PM PDU, make sure:
The PDU is disconnected from a power so
urce and all connected devices are turned off before
replacing a fuse.
Fuses are replaced with an Avocent approved bra
nch circuit fuse class G time delay type with
20A 600 VAC rating.
CAUTION: Avocent recommends using the Avocent fuse replacement kit. Avocent is not responsible for any
issues that may occur using any other vendor’s fuse replacement kit.
Fuses are replaced by qualified personnel.
Fuses are denoted with the following markings on the board: FC1-FC2, FC3-FC4, FC5-FC6,
FC7-FC8, FC9-FC1
0, FC11-FC12, FC13-FC14, FC15-FC16, FC17-FC18, FC19-FC20, FC21-
FC22, FC23-FC24, FC1-FC5, FC2-FC6, FC3-FC7, FC4-FC8 . Refer to Appendix B for fuse(s)
to outlet(s) correlation.
WARNING: There is a risk of explosion if the lithium battery is replaced with an incorrect type. Dispose of used
batteries according to the manufacturer’s instructions.
CAUTION: Double pole/neutral fusing.