Unit CMN
Input Voltage
Input
Current
Output
Voltage
Outlet
Max
Current
Bank Max
Unbalanced
Current
Bank
Max
Balanced
Current
Listed
Branch
Circuit
Protection
PM2008H-
401
PM3008H-
401
1083-
796
EU single
phase 220-240
VAC 2W + PE
50/60 Hz
IEC309
332P6W
32A
220-240
VAC
50/60
Hz
10A
16A (see
note 3)
16A 40A
PM2009H
PM3009H
1083-
792
Single phase
100-240 VAC
2W + PE 50/60
Hz IEC320-
C20
16A
100-240
VAC
50/60
Hz
10A N/A N/A 20A
NOTE 1: When one bank is at a maximum 16A, the other banks shall not exceed 12A per bank.
NOTE 2: When one bank is at a maximum 16A, the other bank(s) shall not exceed 8A total.
NOTE 3: When one bank is at a maximum 16A, the other bank(s) shall not exceed 16A total.
NOTE 4: When one bank is at a maximum 32A, the other banks shall not exceed 13A per bank.
NOTE 5: When one bank is at a maximum 32A, the other banks shall not exceed 23A per bank.
Environmental
Operating Temperature 10ºC to 45ºC (50ºF to 113ºF)
Storage Temperature -40ºC to 65ºC (-40ºF to 149ºF)
Relative Humidity
20% to 80% (non-condensing) across the operating
temperature range; 5% to 95% (non-condensing) across the
non-operating temperature range
Dimensions
Form Factor 0U, 1U rack mountable
Weight
7.3 lbs (horizontal high amperage models without power cord),
14.8 lbs (vertical high amperage models without power cord),
5.2 lbs (horizontal low amperage models without power cord),
11 lbs (vertical low amperage models without power cord)
Table B.2: Avocent PM PDU Information